NEC ComplianceNovember 6, 202413 min read

Understanding NEC Voltage Drop Requirements

Complete guide to National Electrical Code voltage drop requirements, recommendations, and practical calculation methods for safe and efficient electrical installations.

What is Voltage Drop?

Voltage drop is the reduction in voltage that occurs as electrical current flows through the resistance of conductors. While ampacity ensures wires don't overheat, voltage drop affects performance and efficiency.

Why Voltage Drop Matters

  • Equipment Performance: Motors may not start or run properly
  • Light Quality: Lamps operate dimmer than rated
  • Energy Efficiency: Wasted power dissipated as heat
  • Appliance Lifespan: Low voltage can damage electronics
  • Code Compliance: Excessive drop violates NEC recommendations

NEC Voltage Drop Standards

NEC Article 210.19(A) Informational Note No. 4

The NEC provides recommendations (not mandatory requirements) for voltage drop:

NEC Recommendations:

  • Branch Circuits: Maximum 3% voltage drop
  • Feeders: Maximum 2% voltage drop
  • Combined (Feeder + Branch): Maximum 5% total

Important Distinction: Recommendation vs. Requirement

While not mandatory under the NEC, these limits are:

  • Considered best practice and industry standard
  • Often enforced by local codes and inspectors
  • Required for optimal equipment performance
  • Essential for warranty compliance on many devices
  • May become mandatory in future NEC editions

Calculating Voltage Drop

Basic Voltage Drop Formula

Single-Phase Formula:

VD = 2 × K × I × L / CM

Three-Phase Formula:

VD = 1.732 × K × I × L / CM

  • VD = Voltage drop (volts)
  • K = Resistivity constant (12.9 for copper, 21.2 for aluminum)
  • I = Current (amperes)
  • L = One-way length (feet)
  • CM = Wire circular mils

Simplified Formula Using Wire Resistance

Easier Method:

VD = 2 × I × R × L

  • VD = Voltage drop (volts)
  • I = Current (amperes)
  • R = Wire resistance (ohms per 1000 feet)
  • L = One-way length (thousands of feet)
  • 2 = Accounts for round trip (hot and neutral)

Wire Resistance Table

AWG SizeCopper (Ω/1000ft)Aluminum (Ω/1000ft)
14 AWG3.075.06
12 AWG1.933.18
10 AWG1.212.00
8 AWG0.7641.26
6 AWG0.4910.808
4 AWG0.3080.508
2 AWG0.1940.319
1/0 AWG0.1220.201

Step-by-Step Voltage Drop Calculation

Example 1: Residential Branch Circuit

Given:

  • Circuit: 120V, 20A continuous load
  • Wire: 12 AWG copper
  • Distance: 75 feet one-way

Calculation:

  • Wire resistance: 1.93 Ω/1000ft
  • VD = 2 × 20A × 1.93 × (75/1000)
  • VD = 2 × 20 × 1.93 × 0.075
  • VD = 5.79 volts

Percentage:

  • % Drop = (5.79 / 120) × 100
  • % Drop = 4.83% ⚠️ EXCEEDS 3% LIMIT
  • Solution: Upsize to 10 AWG

Example 2: Corrected With Larger Wire

Using 10 AWG Instead:

  • Wire resistance: 1.21 Ω/1000ft
  • VD = 2 × 20A × 1.21 × 0.075
  • VD = 3.63 volts
  • % Drop = (3.63 / 120) × 100
  • % Drop = 3.03% ✓ Just slightly over, acceptable

Example 3: 240V Circuit (Better Performance)

Given:

  • Circuit: 240V, 30A load
  • Wire: 10 AWG copper
  • Distance: 100 feet one-way

Calculation:

  • VD = 2 × 30A × 1.21 × 0.10 = 7.26 volts
  • % Drop = (7.26 / 240) × 100
  • % Drop = 3.03% ✓ Meets 3% guideline
  • Note: Higher voltage = lower percentage drop for same wire

Voltage Drop Limits by Application

Critical Applications (1-2% Maximum)

  • Medical equipment and life safety systems
  • Computer and server rooms
  • Precision electronic equipment
  • Emergency lighting circuits

Standard Applications (3% Maximum)

  • General lighting circuits
  • Receptacle outlets
  • Most residential circuits
  • Commercial branch circuits

Acceptable with Documentation (3-5%)

  • Some motor circuits (verify manufacturer specs)
  • Temporary installations
  • Long-distance feeders when combined drop is under 5%

Practical Wire Sizing Guidelines

When to Upsize Wire for Voltage Drop

Distance Guidelines (120V circuits):

  • Under 50 feet: Standard ampacity sizing usually sufficient
  • 50-100 feet: Check voltage drop, may need to upsize 1 gauge
  • 100-150 feet: Likely need to upsize 1-2 gauges
  • Over 150 feet: Calculate voltage drop, may need 2-3 gauge upsize

Quick Reference: Maximum Run Lengths

Wire Size15A @ 120V20A @ 120V30A @ 240V
14 AWG50 ft
12 AWG80 ft60 ft
10 AWG130 ft95 ft80 ft
8 AWG200 ft150 ft125 ft
6 AWG300+ ft240 ft195 ft

* Maximum one-way distances to stay under 3% voltage drop

Special Scenarios

Motor Circuits

Motors are particularly sensitive to voltage drop:

  • Starting current can be 6-8× running current
  • Low voltage prevents motors from starting
  • Running at low voltage causes overheating
  • Recommend 2% maximum for motor feeders

LED Lighting

LED drivers can be sensitive to voltage variations:

  • Some drivers have wide voltage tolerance (100-277V)
  • Others are voltage-sensitive and may flicker
  • Dimming circuits especially critical
  • Verify driver specifications before installation

Long Distance Feeders

For sub-panels and outbuildings:

  • Feeder limited to 2%, branch circuits to 3%
  • Combined total should not exceed 5%
  • Consider using higher voltage (240V vs 120V)
  • May be more economical to upsize feeder significantly

Voltage Drop Mitigation Strategies

1. Upsize Conductors

Most common solution. Going up one or two wire gauges typically resolves voltage drop issues.

2. Use Higher Voltage

240V circuits have half the percentage drop of 120V circuits for the same load and wire size.

3. Reduce Circuit Length

  • Relocate sub-panel closer to loads
  • Use multiple shorter circuits instead of one long circuit
  • Strategic panel placement in building design

4. Use Copper Instead of Aluminum

Copper has 37% lower resistance than aluminum for the same gauge.

5. Reduce Connected Load

If possible, distribute loads across multiple circuits to reduce current per circuit.

Common Voltage Drop Mistakes

1. Only Checking Ampacity

The most common error. Wire may be safe from overheating but still have excessive voltage drop.

2. Forgetting the Round Trip

Voltage drop occurs in both hot and neutral conductors. Always multiply by 2 for single-phase.

3. Using Nominal Voltage

Calculate drop as percentage of actual supply voltage (typically 120V or 240V), not nameplate.

4. Ignoring Temperature Effects

Wire resistance increases with temperature. Hot environments increase voltage drop slightly.

Inspection and Troubleshooting

Symptoms of Excessive Voltage Drop

  • Lights dimming when loads turn on
  • Motors struggling to start
  • Electronic devices malfunctioning
  • Warm wire insulation even at low current
  • Inconsistent equipment performance

Measuring Voltage Drop

  • Measure voltage at panel with load off
  • Measure voltage at load with full load running
  • Difference is voltage drop
  • Should be under 3% for branch circuits

Tools and Calculators

Use our Voltage Drop Calculator to quickly determine if your wire size is adequate for your circuit length and load. The calculator automatically applies the correct formulas and provides recommendations.

Conclusion

While the NEC voltage drop limits are recommendations rather than strict requirements, following them is essential for proper equipment operation, energy efficiency, and professional installations. Always calculate voltage drop for circuits over 50 feet, and don't hesitate to upsize wire when needed—the small additional cost of larger wire is far less than the problems caused by excessive voltage drop.

Remember: meeting ampacity requirements ensures safety, but controlling voltage drop ensures performance. Both are critical for successful electrical installations.

Wire Gauge Calculator in Your Language

Our wire gauge calculator is available in multiple languages: