TechnicalNovember 22, 202410 min read

Temperature Derating Factors for Wire Ampacity

Learn how to properly apply temperature correction and conductor bundling adjustment factors to ensure safe wire ampacity calculations.

Why Derating is Critical

Wire ampacity tables in the NEC assume ideal conditions: 30°C (86°F) ambient temperature with no more than three current-carrying conductors in a raceway. Real-world installations rarely meet these conditions, requiring derating calculations to prevent overheating and ensure safety.

Understanding Wire Heat Generation

When current flows through wire, electrical resistance generates heat. Wire insulation is rated for maximum temperature it can withstand continuously. Exceeding this temperature causes:

  • Insulation degradation and breakdown
  • Increased resistance and voltage drop
  • Fire hazards from overheating
  • Shortened wire lifespan
  • Equipment damage

Wire Temperature Ratings

Insulation TypeMax TempCommon Applications
TW, UF60°C (140°F)Older installations, underground
THWN, THHN, NM-B75°C (167°F)Most residential/commercial
THHN (dry), XHHW90°C (194°F)High-temperature environments

Ambient Temperature Correction

NEC Table 310.15(B)(1) provides correction factors when ambient temperature differs from 30°C (86°F).

Temperature Correction Factors

Ambient Temp60°C Wire75°C Wire90°C Wire
10°C (50°F)1.291.201.15
20°C (68°F)1.151.111.08
30°C (86°F)1.001.001.00
40°C (104°F)0.820.880.91
50°C (122°F)0.580.750.82
60°C (140°F)0.580.71
70°C (158°F)0.58

Common High-Temperature Locations

  • Attics: Can reach 60-70°C (140-158°F) in summer
  • Rooftops: Direct sun exposure, 50-65°C (122-149°F)
  • Near furnaces/boilers: 40-50°C (104-122°F)
  • Engine rooms: 45-55°C (113-131°F)
  • Industrial ovens: Can exceed 70°C (158°F)

Conductor Bundling Adjustment Factors

When multiple current-carrying conductors are bundled together in a raceway, cable, or conduit, they generate cumulative heat. NEC Table 310.15(C)(1) provides adjustment factors.

Number of ConductorsAdjustment Factor% of Base Ampacity
1-31.00100% (no adjustment)
4-60.8080%
7-90.7070%
10-200.5050%
21-300.4545%
31-400.4040%
41+0.3535%

Important Notes on Conductor Counting

  • Count only current-carrying conductors (exclude grounds and neutrals in balanced loads)
  • Equipment grounding conductors are never counted
  • Neutral wires count only if they carry unbalanced current or harmonics
  • Spare conductors don't count unless energized

Applying Multiple Derating Factors

When both ambient temperature and conductor bundling require derating, multiply both factors together:

Adjusted Ampacity = Base Ampacity × Temperature Factor × Bundling Factor

Example Calculation:

  • Wire: 12 AWG copper (75°C insulation)
  • Base ampacity: 25A
  • Ambient temp: 50°C (122°F) → Factor = 0.75
  • Conductors in conduit: 6 → Factor = 0.80
  • Adjusted ampacity = 25A × 0.75 × 0.80 = 15A

Practical Application Examples

Example 1: Attic Installation

Scenario:

  • Location: Attic with 60°C ambient temperature
  • Conductors: 3 current-carrying (one circuit)
  • Wire: 14 AWG copper, THHN (90°C rating)

Calculation:

  • Base ampacity (90°C column): 30A
  • Temperature correction (60°C): 0.71
  • Bundling factor (3 conductors): 1.00
  • Adjusted ampacity = 30A × 0.71 = 21.3A
  • Conclusion: Still suitable for 15A circuit, but verify with 15A breaker terminal rating (usually 75°C)

Example 2: Multiple Circuits in Conduit

Scenario:

  • Location: Indoor at 30°C ambient
  • Conductors: 9 current-carrying (three 3-wire circuits)
  • Wire: 12 AWG copper, THWN (75°C rating)

Calculation:

  • Base ampacity (75°C column): 25A
  • Temperature correction (30°C): 1.00
  • Bundling factor (7-9 conductors): 0.70
  • Adjusted ampacity = 25A × 1.00 × 0.70 = 17.5A
  • Problem: Not suitable for 20A circuit!
  • Solution: Upsize to 10 AWG (35A × 0.70 = 24.5A)

Example 3: Commercial Rooftop Installation

Scenario:

  • Location: Rooftop conduit, 55°C ambient in summer
  • Conductors: 12 current-carrying (four 3-wire circuits)
  • Required load: 30A continuous

Calculation:

  • Continuous load factor: 30A × 1.25 = 37.5A minimum
  • Try 8 AWG copper, 90°C: Base = 55A
  • Temperature correction (55°C): 0.76
  • Bundling factor (10-20 conductors): 0.50
  • Adjusted = 55A × 0.76 × 0.50 = 20.9A
  • Not sufficient! Try larger size...
  • Try 4 AWG copper, 90°C: Base = 95A
  • Adjusted = 95A × 0.76 × 0.50 = 36.1A
  • Still not enough for 37.5A requirement!
  • Try 3 AWG copper, 90°C: Base = 110A
  • Adjusted = 110A × 0.76 × 0.50 = 41.8A
  • ✓ Meets 37.5A requirement

Special Considerations

Terminal Temperature Ratings

Even if wire is rated 90°C, breakers and devices often have 75°C terminals. You must:

  • Use 90°C rating for derating calculations
  • Use 75°C rating for final ampacity check
  • Verify device terminal ratings before sizing

Continuous Loads

Don't forget the 125% continuous load factor applies AFTER derating:

⚠️ Correct Order of Operations

  1. Start with base ampacity from NEC tables
  2. Apply temperature correction factor
  3. Apply bundling adjustment factor
  4. Result must be ≥ 125% of continuous load

Sunlight and Direct Heating

Conduit exposed to direct sunlight can be 15-30°C hotter than air temperature. Use conservative estimates.

Common Derating Mistakes

1. Using Wrong Base Ampacity

Always use the ampacity from the column matching your wire's insulation temperature rating.

2. Forgetting to Derate

Assuming table values work in all conditions is dangerous and violates code.

3. Incorrect Conductor Counting

Don't count equipment grounds. Be careful with neutrals in 3-phase systems.

4. Applying Factors in Wrong Order

Must apply continuous load factor LAST, after all derating calculations.

Tools and Resources

Use our Wire Ampacity Calculator to automatically apply derating factors and determine correct wire sizes for your specific installation conditions.

Conclusion

Temperature derating is not optional—it's required by code and essential for safety. Failing to properly apply correction and adjustment factors can result in dangerous overheating, insulation failure, and fire hazards. Always account for both ambient temperature and conductor bundling when sizing wire, and when in doubt, size up to the next larger gauge.

Wire Gauge Calculator in Your Language

Our wire gauge calculator is available in multiple languages: