Back to Tools
Tool Module

Wire Ampacity Calculator

// CALCULATE MAXIMUM CURRENT CARRYING CAPACITY BASED ON NEC TABLE 310.16 WITH TEMPERATURE AND BUNDLING DERATING FACTORS //

INPUT_PARAMETERS
AMPACITY_RESULT
Base Ampacity (NEC 310.16)
25 A
copper @ 75°C insulation
Combined Derating
100%
Bundle: 100% × Ambient: 100%
Adjusted Ampacity
25 A
After all derating
Recommended Max Breaker Size
15 A
Per NEC 240.4 overcurrent protection
Common Applications for 12 AWG copper
General purpose outlets (20A breaker)
NEC_TABLE_310.16_AMPACITY

Allowable Ampacities of Insulated Conductors (NEC Table 310.16)

Based on not more than three current-carrying conductors in raceway, cable, or earth, ambient temperature of 30°C (86°F).

AWG/kcmilCopperAluminum
60°C75°C90°C60°C75°C90°C
14 AWG152025---
12 AWG202530152025
10 AWG303540253035
8 AWG405055354045
6 AWG556575405055
4 AWG708595556575
2 AWG951151307590100
1 AWG11013014585100115
1/0 AWG125150170100120135
2/0 AWG145175195115135150
3/0 AWG165200225130155175
4/0 AWG195230260150180205
CONDUCTOR_BUNDLING_DERATING

Conductor Bundling Adjustment Factors (NEC 310.15(C)(1))

1-3

Conductors

100%

4-6

Conductors

80%

7-9

Conductors

70%

10-20

Conductors

50%

21-30

Conductors

45%

31-40

Conductors

40%

41+

Conductors

35%

* Applies to more than three current-carrying conductors in a raceway or cable. Neutral conductors are not counted if they carry only unbalanced current.

UNDERSTANDING_AMPACITY

What is Wire Ampacity?

Ampacity, short for ampere capacity, is the maximum electrical current a conductor can carry continuously without exceeding its temperature rating. This is critical for electrical safety—exceeding ampacity causes overheating, melted insulation, and fire hazards.

Overheating Risk

Exceeding ampacity melts insulation and creates fire hazards

Temperature Based

Higher insulation temp ratings allow more current

NEC Compliant

Table 310.16 is the primary ampacity reference

NEC_310.16_BASE_CONDITIONS

NEC Table 310.16 Base Conditions

The NEC Table 310.16 values are based on specific conditions. When your installation differs, apply correction factors.

ConditionBase AssumptionIf Different
Conductor Count≤3 current-carrying conductorsApply bundling derating factors
Ambient Temperature30°C (86°F)Apply temperature correction factors
Installation TypeRaceway, cable, or direct burialFree air has higher ampacity (Table 310.17)
INSULATION_TEMPERATURE_RATINGS

Insulation Temperature Ratings Explained

60°C

(140°F)

Types: TW, UF

Lowest rating, dry locations only

Limited modern applications

75°C

(167°F)

Types: THW, THWN, XHHW

Most common for commercial

Standard terminal rating

90°C

(194°F)

Types: THHN, THWN-2

Highest ampacity values

Often limited by 75°C terminals

Important: Terminal Temperature Limitation

Even with 90°C wire, NEC 110.14(C) limits ampacity to the lowest temperature rating in the circuit. Most equipment terminals are rated 75°C, so use 75°C column values unless terminals are rated higher.

AMBIENT_TEMPERATURE_CORRECTION

Ambient Temperature Correction Factors

Base ampacity assumes 30°C (86°F) ambient. Apply these correction factors from NEC Table 310.15(B)(1) for different temperatures:

Ambient Temp60°C Wire75°C Wire90°C Wire
21-25°C (70-77°F)108%105%104%
26-30°C (78-86°F)100%100%100%
36-40°C (97-104°F)82%88%91%
46-50°C (115-122°F)58%75%82%

Common High-Temperature Locations

Attics

40-55°C in summer

Rooftops

Direct sun exposure

Boiler Rooms

Near heat sources

Industrial

Process equipment

COPPER_VS_ALUMINUM

Copper vs. Aluminum Conductors

Copper Advantages

  • Higher conductivity (61% better than aluminum)
  • Smaller wire size for same ampacity
  • Better corrosion resistance at terminals
  • Preferred for 14-6 AWG branch circuits

Aluminum Advantages

  • 70% lighter than copper
  • Significantly lower cost per ampere
  • Preferred for feeders and service entrance
  • Modern AA-8000 alloy has improved performance

Note: NEC does not permit aluminum conductors smaller than 12 AWG. For equivalent ampacity, aluminum requires approximately 2 AWG sizes larger than copper. Learn more in our copper vs aluminum guide.

PRACTICAL_EXAMPLES

Ampacity Calculation Examples

Example 1: Standard 20A Kitchen Circuit

12 AWG copper, 75°C insulation, EMT conduit, 30°C ambient

Base Ampacity

25A

Bundle Factor

100%

Temp Factor

100%

Final Ampacity

25A

Result: 12 AWG copper is adequate for a 20A breaker.

Example 2: Attic Fan Circuit (High Temperature)

14 AWG copper, 75°C insulation, attic at 45°C

Base Ampacity

20A

Bundle Factor

100%

Temp Factor

82%

Final Ampacity

16.4A

Result: 14 AWG only provides 16.4A—upgrade to 12 AWG for a 15A circuit in hot attics.

Example 3: Multiple Circuits in Conduit

12 AWG copper, 9 current-carrying conductors (3 × 20A circuits)

Base Ampacity

25A

Bundle Factor

70%

Temp Factor

100%

Final Ampacity

17.5A

Result: 12 AWG inadequate for 20A circuits! Upgrade to 10 AWG (35A × 0.70 = 24.5A).

OVERCURRENT_PROTECTION

Overcurrent Protection Requirements (NEC 240.4)

Wire SizeMax Breaker (Copper)Exception
14 AWG15ANEC 240.4(D) limits small conductors
12 AWG20ANEC 240.4(D) limits small conductors
10 AWG30ANEC 240.4(D) limits small conductors
8 AWG+Per AmpacityNext standard size up to 800A allowed
FREQUENTLY_ASKED_QUESTIONS

What is the difference between ampacity and current rating?

Ampacity is the maximum continuous current a conductor can carry without exceeding its temperature rating. Current rating typically refers to the maximum current an overcurrent device (breaker or fuse) can handle. Wire ampacity must meet or exceed the circuit's current rating.

Why can't I use the 90°C column for my 90°C rated wire?

NEC 110.14(C) limits conductor ampacity based on the lowest temperature rating in the circuit, including equipment terminals. Most equipment is rated for 75°C, requiring use of 75°C ampacity values even with 90°C wire. The 90°C rating can be used for derating calculations but final ampacity is limited by terminations.

Do ground wires count toward conductor bundling?

No, equipment grounding conductors are not counted as current-carrying conductors for bundling derating purposes. Similarly, neutral conductors that carry only unbalanced current from other conductors of the same circuit are not counted.

Can I use 14 AWG aluminum wire?

The NEC does not provide ampacity values for aluminum conductors smaller than 12 AWG in Table 310.16. Aluminum 14 AWG is not typically used or available for building wiring applications due to concerns about reliability and connection issues at small sizes.

How does continuous load affect ampacity requirements?

For continuous loads (operating 3 hours or more), NEC 210.20 and 215.3 require the conductor ampacity to be at least 125% of the continuous load. This effectively means using only 80% of the conductor's ampacity for continuous loads. Our calculator provides base ampacity; multiply by 0.8 for continuous load applications.

Related Tools
AUTHORITATIVE_REFERENCES

For official ampacity standards and additional technical information, consult these authoritative sources: