Back to Tools
NEC Compliant

Voltage Drop Calculator

// CALCULATE VOLTAGE DROP AND SELECT OPTIMAL WIRE SIZE //

INPUT_PARAMETERS
A
ft
ANALYSIS_RESULT
NEC StatusEXCEEDS 3% LIMIT
Voltage Drop
7.72 V
6.43%
Voltage at Load
112.28 V
Power Loss
154.40 W
Wire Resistance
0.3860 Ω
Recommendation

Consider using a larger wire gauge or shorter run to reduce voltage drop below 3%.

WIRE_RESISTANCE_TABLE

Wire Resistance Reference (NEC Chapter 9 Table 8)

Resistance values in ohms per 1,000 feet at 75°C operating temperature. These values are essential for accurate voltage drop calculations in electrical circuit design.

AWG SizeCopper (Ω/1000ft)Aluminum (Ω/1000ft)Typical Application
14 AWG3.075.06Lighting circuits (15A)
12 AWG1.933.18General outlets (20A)
10 AWG1.211.99Dryers, water heaters (30A)
8 AWG0.7641.26Ranges, EV chargers (40-50A)
6 AWG0.4910.808Subpanels, HVAC (55-65A)
4 AWG0.3080.508Large appliances (70-85A)
2 AWG0.1940.319Service entrance (95-115A)
1/0 AWG0.1220.201Main service (125-150A)
4/0 AWG0.06080.100Large service (180-230A)
WHAT_IS_VOLTAGE_DROP

Understanding Voltage Drop in Electrical Circuits

Voltage drop is one of the most critical factors in electrical circuit design and is essential knowledge for electricians, engineers, and anyone working with electrical installations. When electrical current flows through a conductor, some of the electrical energy is converted to heat due to the conductor's resistance. This energy loss manifests as a reduction in voltage between the source and the load.

Motor Failure

Overheating & stalling

Light Dimming

Flickering & reduced output

Energy Waste

Heat loss in wires

Code Violation

Failed inspections

NEC_VOLTAGE_DROP_REQUIREMENTS

National Electrical Code (NEC) Requirements

The NFPA 70 National Electrical Code provides recommendations for acceptable voltage drop levels per NEC 210.19(A) and 215.2(A) NFPA 70 National Electrical Code:

3%

Branch Circuits

From panel to outlets, lights, and appliances

3%

Feeder Circuits

From service entrance to panelboard

5%

Combined Total

Feeder + branch from source to load

Note: While these are recommendations rather than mandatory requirements, they represent industry best practices. Many local jurisdictions enforce these limits, and inspectors commonly flag installations that exceed them.

VOLTAGE_DROP_FORMULAS

Voltage Drop Calculation Formulas

Single-Phase Circuit

VD = 2 × I × R × L ÷ 1000

Factor of 2 = round-trip distance

Used for 120V and 240V single-phase

Three-Phase Circuit

VD = √3 × I × R × L ÷ 1000

√3 ≈ 1.732 phase factor

Used for 208V, 480V three-phase

VariableDescriptionUnit
VDVoltage DropVolts (V)
ICurrent (load amperage)Amperes (A)
RWire resistance (from NEC Table 8)Ω per 1000 ft
LOne-way wire lengthFeet (ft)
FACTORS_AFFECTING_VOLTAGE_DROP

Key Factors That Affect Voltage Drop

1

Wire Gauge (AWG)

Larger wires (lower AWG numbers) have lower resistance. 10 AWG has ~40% less resistance than 12 AWG. Increasing wire gauge is the most common solution for excessive voltage drop.

2

Wire Length

Voltage drop increases proportionally with length. A 100-foot run has twice the voltage drop of a 50-foot run. Long runs to outbuildings require careful calculation.

3

Current Load

Higher current = greater voltage drop. High-current applications like EV chargers and welders are particularly sensitive to voltage drop issues.

4

Conductor Material

Copper has ~61% the resistance of aluminum. Aluminum requires 2 AWG sizes larger for equivalent performance but costs less for large feeders.

HOW_TO_REDUCE_VOLTAGE_DROP

Practical Strategies to Reduce Voltage Drop

StrategyEffectBest For
Increase Wire Gauge~26% reduction per size increaseLong runs, high current loads
Shorten Wire RunsProportional reductionNew construction, layout planning
Use Higher Voltage240V = half the % drop of 120VHigh-power equipment
Add SubpanelReduces branch circuit lengthsGarages, workshops, outbuildings
Use Copper (vs Aluminum)~39% lower resistanceRetrofit, limited conduit space
Parallel ConductorsHalves resistance (2 conductors)Large service entrances
REAL_WORLD_EXAMPLES

Common Voltage Drop Scenarios

Detached Garage Workshop

100 ft

Distance

50A

Subpanel

240V

Voltage

4 AWG

Recommended

6 AWG gives 3.4% drop (fails). 4 AWG reduces to 2.1% (compliant). Suitable for power tools and welding.

Level 2 EV Charger

80 ft

Distance

40A

Load

240V

Voltage

8 AWG

Minimum

8 AWG at 80 ft = 2.9% (acceptable). At 120 ft, upgrade to 6 AWG required. See our EV charger wiring guide.

Farm Irrigation Pump

500 ft

Distance

20A

Load

240V

Voltage

4 AWG

Minimum

Long agricultural runs require significant wire sizing. 4 AWG keeps drop under 5%. Consider solar system sizing needs as well.

WHY_VOLTAGE_DROP_MATTERS

Why Accurate Voltage Drop Calculations Matter

Equipment Performance

Motors and equipment operate within specified voltage ranges. Low voltage causes inefficiency, overheating, and premature failure.

Energy Efficiency

Voltage drop = wasted energy as heat. Higher drop means higher electricity bills and increased carbon footprint.

Code Compliance

Many jurisdictions enforce NEC recommendations. Failed inspections delay projects and require costly corrections.

FREQUENTLY_ASKED_QUESTIONS

What is an acceptable voltage drop percentage?

The NEC recommends a maximum of 3% voltage drop for branch circuits and 5% total for combined feeder and branch circuits. However, for sensitive electronic equipment, a lower voltage drop of 2% or less may be desirable.

How does voltage drop affect LED lights?

LED lights are generally more tolerant of voltage variations than incandescent bulbs. However, significant voltage drop can still cause dimming, color temperature shifts, and reduced lifespan. Keep voltage drop below 3% for lighting circuits.

Should I use copper or aluminum wire?

Copper has lower resistance and is preferred for most applications. Aluminum is cost-effective for large feeders and service entrances but requires larger wire sizes (typically 2 AWG numbers larger than copper for the same ampacity).

How do I calculate voltage drop for a motor circuit?

For motor circuits, use the full-load current rating from the motor nameplate. For motor starting, voltage drop can be higher temporarily, but the running voltage should remain within 3% of rated voltage.

Does conduit type affect voltage drop?

The conduit type (EMT, PVC, rigid) does not directly affect voltage drop. However, it can affect heat dissipation, which indirectly impacts conductor resistance. Steel conduits may also introduce additional impedance in AC circuits due to magnetic effects.

Related Tools
AUTHORITATIVE_REFERENCES

For official standards and additional technical information, consult these authoritative sources: