Mistake #1: Ignoring Voltage Drop
The most common and dangerous mistake. Many installers only check ampacity and ignore voltage drop, leading to:
- Dim lights and poor performance
- Motor damage from low voltage
- Wasted energy and higher bills
- Potential code violations
Solution: Always calculate voltage drop for runs over 50 feet. Use our Voltage Drop Calculator.
Mistake #2: Not Accounting for Continuous Loads
NEC requires continuous loads (3+ hours) be calculated at 125% of actual current.
Example: A 16A continuous load requires wire sized for 20A minimum.
Mistake #3: Forgetting Temperature Derating
- Attic installations can exceed 120°F
- Bundled conductors generate heat
- Multiple circuits in conduit require derating
Solution: Apply NEC temperature correction factors.
Mistake #4: Improper Aluminum Terminations
Using standard devices with aluminum wire causes:
- Loose connections over time
- Overheating and fire hazards
- Oxidation and high resistance
Solution: Always use CO/ALR rated devices and anti-oxidant compound.
Mistake #5: Oversizing Breakers
Wire must be protected by properly sized overcurrent devices. Never install a larger breaker to "solve" tripping issues.
Mistake #6: Mixing Wire Sizes
All current-carrying conductors in a circuit must be the same size unless specifically designed otherwise.
Mistake #7: Not Planning for Future Expansion
Installing slightly larger wire initially costs little more but provides flexibility for future upgrades.
Mistake #8: Incorrect Grounding
- Ground wire must be sized per NEC Table 250.122
- Oversized phase conductors require larger ground
- Separate grounding for sub-panels
How to Avoid These Mistakes
- Use proper calculation tools and tables
- Account for all derating factors
- Follow NEC requirements strictly
- When in doubt, size up one gauge
- Have work inspected by qualified electrician