Elevator CircuitsUpdated November 14, 202614 min readHommer Zhao · Founder & General Manager

Elevator Wire Size NEC: 140% Rule, 620.13 & Feeder Examples

Intermittent elevator duty: 140% for continuous-rated motors, 85% for 5/15 min, 90% for 30/60 min. Controller inputs use NEC 620.13(B).

Is elevator wire sized at 140% of nameplate current (NEC)?

TL;DR: 140% applies only to a continuous-rated motor used in intermittent elevator duty under Table 430.22(E) via NEC 620.13(A). A 5- or 15-minute-rated motor uses 85%; a 30- or 60-minute-rated motor uses 90%. Circuits supplying a controller use controller nameplate amps plus other connected loads under 620.13(B). Multi-car feeders may use Table 620.14 demand factors.

Check voltage drop for your run

Published May 11, 2026. Updated November 14, 2026.

NEC 620.13 conductor ampacity: motor, controller, transformer

  • (A) Single motor: use the percentage of motor nameplate current determined from 430.22(A) and (E). For intermittent elevator duty, select the motor rating column in Table 430.22(E).
  • (B) Single motor controller: use at least the controller nameplate current rating plus all other connected loads. This is the basis for a circuit supplying a modern VFD traction or hydraulic soft-start controller.
  • (C) Single power transformer: use the transformer nameplate rating plus other connected loads.
  • (D) More than one motor, controller or transformer: establish each applicable current basis before summing and adding other connected loads. For motor currents in the sum, the 2008 text also references Table 430.22(E), 430.24 and its Exception No. 1. Confirm the adopted-edition calculation with the engineer of record / AHJ, then evaluate feeder demand under 620.14 where applicable.

The informational note explains that elevator motor currents may exceed nameplate values but are inherently intermittent; conductor heating depends on rms current. The motor’s continuous duty rating is different from its intermittent elevator service. The 140% table entry is not a universal elevator multiplier or the 125% in 430.22(A).

Table 430.22(E) percentages for elevator motors (85%, 90%, 140%)

Motor nameplate ratingIntermittent elevator service percentageMultiplier
5-minute85%0.85
15-minute85%0.85
30- & 60-minute90%0.90
Continuous140%1.40

Minimum conductor ampacity by nameplate current (calculated)

Each result shows minimum ampacity → smallest listed 75 °C copper conductor. Before ambient/bundling correction, voltage drop and terminal limits; calculated by Wire Gauge Calculator on 2026-11-14 from Table 310.16 75 °C copper. Verify terminal temperature under 110.14(C). This motor-percentage table does not replace the controller basis in 620.13(B).

Nameplate A85% result90% result140% result
3025.5 A → 10 AWG (35 A)27.0 A → 10 AWG (35 A)42.0 A → 8 AWG (50 A)
4034.0 A → 10 AWG (35 A)36.0 A → 8 AWG (50 A)56.0 A → 6 AWG (65 A)
5244.2 A → 8 AWG (50 A)46.8 A → 8 AWG (50 A)72.8 A → 4 AWG (85 A)
6051.0 A → 6 AWG (65 A)54.0 A → 6 AWG (65 A)84.0 A → 4 AWG (85 A)
8068.0 A → 4 AWG (85 A)72.0 A → 4 AWG (85 A)112.0 A → 2 AWG (115 A)
10085.0 A → 4 AWG (85 A)90.0 A → 3 AWG (100 A)140.0 A → 1/0 AWG (150 A)

Worked example: three-elevator feeder with Table 620.14 demand factor

Hypothetical: three traction elevators, each with a controller nameplate current of 52 A at 208 V, three-phase. Sum: 3 × 52 = 156 A. Table 620.14 gives a three-car factor of 0.90: 156 × 0.90 = 140.4 A. The smallest listed 75 °C copper conductor is 1/0 AWG (150 A), before other connected loads, correction, adjustment and terminal limits.

Whether the 125%-of-largest-motor rule in 430.24 applies on top of the duty-cycle percentage for a multi-elevator feeder is debated. Confirm the calculation approach with the engineer of record / AHJ before final selection.

At 150 ft one way, a resistance-only voltage-drop estimate is 1.732 × 140.4 A × 0.122 Ω/1000 ft × 150 ft ≈ 4.45 V, or 2.1% of 208 V. The resistance is the 1/0 uncoated copper DC resistance at 75 °C from NEC Chapter 9 Table 8. With 2/0 copper at 0.0967 Ω/1000 ft, the estimate is 3.53 V, or 1.7%. This simplified calculation does not model AC reactance, power factor, starting current or source impedance.

Feeder demand by number of cars (52 A controllers)

CarsSum of controller ATable 620.14 factorDemand A → smallest 75 °C copper
1521.0052.0 A → 6 AWG (65 A)
21040.9598.8 A → 3 AWG (100 A)
31560.90140.4 A → 1/0 AWG (150 A)
42080.85176.8 A → 3/0 AWG (200 A)
52600.82213.2 A → 4/0 AWG (230 A)
63120.79246.5 A → 250 kcmil (255 A)

Table 620.14 factors for 1–10 or more elevators are 1.00, 0.95, 0.90, 0.85, 0.82, 0.79, 0.77, 0.75, 0.73 and 0.72. Its informational note bases them on a 50% duty cycle. One elevator gets no reduction. These hypothetical feeder results exclude other connected loads and the unresolved 430.24 coordination question above.

Elevator load schedule: what to get from the supplier

Ask for the elevator power data sheet before pricing wire. A typical schedule will list voltage, phase, full load amps, starting current or drive input current, recommended disconnect size, maximum fuse or breaker size, and separate branch circuits for cab lighting or machine-room receptacles. If the controller nameplate current is unavailable, obtain the manufacturer's input-current rating before final sizing under NEC 620.13(B). Label any interim estimate as provisional.

Hypothetical example: a 480V, three-phase hydraulic elevator controller lists 42A input and a 70A maximum overcurrent device, with a 180 ft one-way feeder. Check the manufacturer conductor requirements, applicable motor and elevator rules, terminal ratings, and derating before selecting wire. Running current alone does not establish starting voltage: calculate it from starting current, conductor impedance, and source data. These inputs do not establish a final choice between 4 AWG and 3 AWG copper.

Elevator circuit decisions: load basis and NEC references

Use this table as a decision map before entering numbers in the calculator. The exact conductor size still depends on insulation, terminal temperature, raceway count, ambient temperature, and manufacturer instructions.

Elevator CircuitTypical Load BasisPrimary Code CheckCommon Wire-Sizing RiskPractical Example
Traction elevator feederController input amps and drive dataNEC 620 plus Article 430 coordinationStarting or regenerative drive behavior ignoredHypothetical 52 A controller: compare ampacity and voltage drop separately
Hydraulic pump feederPump motor/control nameplateNEC 620.13(B), 620.51 disconnect; 620.61 overcurrent protectionLong riser sized only from ampacityHypothetical 42 A controller: verify corrections and starting conditions
Cab lighting circuitLighting and ventilation VANEC 620.22 branch-circuit requirementsShared circuit used where a dedicated circuit is requiredUse the car lighting/receptacle/ventilation schedule
Machine-room receptacleService receptacle ratingNEC 620.23; verify applicable GFCI requirements under 620.85 in the adopted editionOmitted or routed with elevator power without coordinationCheck machine-room/control-space lighting and receptacles
Hoistway pit lighting/receptaclesPit lighting and receptacle scheduleNEC 620.24Pit circuits omitted from the load scheduleReview separately from car and machine-room circuits
Equipment grounding conductorFeeder overcurrent deviceNEC 250.122Phase conductors upsized without reviewing EGC requirementsCheck the applicable NEC 250.122 protective-device basis and motor-circuit provisions
Fire service or shunt trip controlsControl transformer and alarm interfaceNEC 620.51 and local elevator/fire requirementsControl/power routing not checked against the equipment listing and adopted codeCoordinate controller and fire-interface documentation

Elevator conductor ampacity: terminal limits and correction

Start with conductor ampacity at the terminal temperature actually allowed by the equipment. Use 75 °C ampacities only when the terminal limits under 110.14(C) permit them. Select from NEC Table 310.16, then apply correction and adjustment as applicable if the elevator feeder shares a raceway with other current-carrying conductors or passes through a hot mechanical penthouse.

Hypothetical example: a 208V, 3-phase traction elevator controller lists 52A input current and an 80A fused disconnect (hypothetical). If the conductor ampacity needs to clear the controller load at 75 °C, 6 AWG copper at 65A might look acceptable before correction. If conductor-count adjustment or ambient correction applies, recalculate the effective ampacity before choosing a conductor; the correction inputs are not specified in this hypothetical example.

Do Not Skip Manufacturer Limits

Verify the controller's specified protective-device type and maximum rating for its supply circuit. Increasing conductor size for voltage drop does not change those equipment limits.

Elevator voltage drop and starting performance

Compare running and starting voltage at the elevator terminals against supplier requirements and the project design target. A running-current calculation cannot establish acceleration performance; obtain starting current and source data before making that decision.

For a hypothetical 480V, 3-phase, 42A hydraulic elevator at 180 feet one way, a rough copper voltage-drop check is: volts drop equals 1.732 x current x conductor resistance x distance. Using 4 AWG at 0.308 ohm per 1000 ft (uncoated copper DC resistance at 75 °C from NEC Chapter 9 Table 8), the estimate is 1.732 x 42 x 0.308 x 180 / 1000, or about 4.0 V. That is 0.84% at 480V during running current. If the controller draws much higher current during start, the supplier may still ask for a larger conductor or a drive setting review.

Elevator disconnects, grounding and raceway fill

NEC 620.51 covers disconnecting means; 620.61 covers overcurrent protection. Check the adopted edition of 620.51 for the applicable disconnect location and operating requirements. The feeder conductors must fit the selected lugs and raceway, and the adopted edition of NEC 250.122 should be reviewed for the equipment grounding conductor, including the applicable protective-device basis, motor-circuit provisions and requirements when phase conductors are increased for voltage drop.

Raceway and pull planning can be as important as ampacity. A 3 AWG copper, 3-phase feeder with ground may fit easily in one conduit size and become a difficult pull in another, especially in a tall riser with offsets. Before issuing drawings, check the conduit fill calculator, then verify long-pull layout with the pull box sizing calculator. For load and conductor comparisons, use the main wire gauge calculator and the voltage drop calculator.

Elevator overcurrent protection and selective coordination (NEC 620.61, 620.62)

NEC 620.61 sends elevator overcurrent protection back to Article 430. Motor and branch-circuit overload protection follows Article 430, Part III; 620.61(B)(1) treats elevator driving-machine motor duty as intermittent, and such motors are permitted to be protected against overload under 430.33. Motor feeder short-circuit and ground-fault protection follows Article 430, Part V, and motor branch-circuit short-circuit and ground-fault protection follows Article 430, Part IV. Operating devices and control and signaling circuits have their own overcurrent rules in 620.61(A).

Where one feeder supplies more than one driving-machine disconnecting means, 620.62 requires the overcurrent devices in each disconnect to be selectively coordinated with the supply-side devices. That affects the feeder breaker and disconnect fuse choices in the three-elevator example above, so the protective-device schedule and the conductor size should be reviewed together. Protective-device ratings do not replace conductor ampacity calculations. Check each controller's specified protection limits for its individual supply circuit. Review common-feeder protection separately under NEC 620.61(C), Article 430 Part V, and the selective-coordination requirements of 620.62.

Elevator feeder worked examples 1–3 (hypothetical)

Example 1: 480V Hydraulic Elevator Feeder

Hypothetical: the elevator schedule lists 42A input, 480V 3-phase, 70A maximum overcurrent protection, 75 °C terminals, and a 180-foot one-way feeder. Under 620.13(B), 42 A alone fits within 8 AWG copper’s 50 A rating at 75 °C before other loads and corrections. This hypothetical comparison uses 4 AWG for additional ampacity and voltage-drop margin. Voltage drop at running current is under 1%, but the contractor should still confirm starting current and drive tolerance with the supplier. A larger conductor requires a new calculation against the actual installation conditions.

Example 2: 208V Traction Elevator In A Mid-Rise Building

Hypothetical: a traction elevator controller lists 52A input at 208V, with an 80A fused disconnect and a 210-foot feeder. The 52 A controller basis initially fits 6 AWG copper at 65 A before other loads and corrections. At 210 feet, compare larger sizes using the supplier’s voltage tolerance and running/starting data; an 80 A disconnect does not determine conductor ampacity. Calculated comparison, assuming three-phase operation and uncoated copper DC resistance at 75 °C: at 52 A and 210 ft one way, 4 AWG gives 1.732 × 52 × 0.308 × 210 / 1000 = 5.83 V, or 2.80% of 208 V. This resistance-only estimate does not establish starting performance.

Example 3: why voltage and route length cannot size auxiliary circuits

Hypothetical: a project has separate 120 V car lighting and machine-room receptacle circuits with 140-foot routes. Build their load schedules separately from the elevator power feeder. Check car lighting, receptacles and ventilation under 620.22, machine-room/control-space lighting and receptacles under 620.23, and hoistway pit lighting/receptacles under 620.24. The 120 V supply and 140 ft route are insufficient to select a conductor: each circuit’s load current is still required. Calculate each circuit’s ampacity and voltage drop before selecting conductors.

Common elevator wire sizing mistakes

  • Using elevator horsepower instead of the controller input current and manufacturer protection data.
  • Forgetting NEC 620 branch-circuit requirements for cab lighting, receptacles, ventilation, and controls.
  • Checking NEC Table 310.16 but ignoring terminal temperature, rooftop heat, or conductor-count derating.
  • Upsizing phase conductors for voltage drop without reviewing the adopted NEC 250.122 requirements for the equipment grounding conductor.
  • Leaving pull boxes, disconnect working space, or conduit fill until after the wire size is already ordered.

Elevator wire sizing frequently asked questions

Is elevator wire sized at 140% under the NEC?

Only a continuous-rated motor used in intermittent elevator service uses 140% of motor nameplate current under Table 430.22(E) via 620.13(A). The table uses 85% for 5- or 15-minute-rated motors and 90% for 30- or 60-minute-rated motors. Circuits supplying a controller use its nameplate current plus other connected loads under 620.13(B).

When does the 140% rule not apply to an elevator?

It does not apply to every elevator circuit. Intermittent elevator service with a 5- or 15-minute-rated motor uses 85%, and a 30- or 60-minute-rated motor uses 90%. Conductors supplying a controller use its nameplate current rating plus all other connected loads under NEC 620.13(B). Do not substitute a blanket 125% multiplier for this distinction.

Do Table 620.14 demand factors apply to one elevator?

Table 620.14 lists a factor of 1.00 for one elevator, so it provides no demand reduction for a single elevator. Multi-car feeder factors depend on the number of elevators; confirm the adopted edition and other connected loads.

What NEC article covers elevator feeder wire sizing?

NEC Article 620 covers elevator circuits. Use 620.13 for the motor, controller or transformer ampacity basis, 620.14 for feeder demand, Table 310.16 for conductor ampacity, 250.122 for equipment grounding conductors, and 110.14(C) for terminal temperature limits.

What wire size is typical for a 70A elevator feeder?

If the required conductor ampacity is 70 A, 4 AWG copper provides 85 A at 75 °C before correction and adjustment. A 70 A overcurrent device alone does not establish conductor ampacity; confirm the controller load, terminal limits and voltage drop.

Should elevator feeder voltage drop be limited to 3%?

The information used here does not establish a universal 3% requirement for elevator feeders. Check the adopted code, supplier voltage tolerance and project design target, then evaluate running and starting conditions separately.

Can I use aluminum conductors for elevator feeders?

Confirm that the equipment terminals and manufacturer instructions permit aluminum, then select conductors using the applicable ampacity and resistance data. The copper tables in this article do not size aluminum feeders.

How is the elevator equipment grounding conductor sized?

Review the adopted edition of NEC 250.122 for the equipment grounding conductor, including the applicable protective-device basis, motor-circuit provisions and requirements when phase conductors are increased for voltage drop. The phase-conductor tables here do not size the equipment grounding conductor.

Do elevator cab lights need a separate circuit?

Yes. NEC 620.22(A) provides a separate branch circuit for car lighting, receptacles and ventilation; this does not mean a separate circuit for each of those loads. Machine-room and control-space lighting and receptacles are covered by 620.23; hoistway pit lighting and receptacles are covered by 620.24. Confirm the required circuit arrangement in the adopted edition.

Which calculator should I use first for an elevator feeder?

Establish the required ampacity from the applicable nameplate basis first. Use the wire gauge calculator for conductor comparisons, then the voltage drop calculator with the actual one-way distance, followed by conduit fill and pull box checks.

Elevator feeder sizing: next steps and tools

Elevator wiring needs a coordinated submittal, not a single wire-size guess. Enter the manufacturer input amps, voltage, phase, conductor material, terminal temperature, and one-way distance in the calculator. Then confirm disconnect limits, grounding, conduit fill, and branch-circuit requirements before material release. For a broader motor workflow, compare this article with the motor circuit wire sizing guide and the voltage drop vs ampacity guide.

For project-specific support, use the elevator feeder wire sizing service page or contact us with your elevator schedule.

Sources and method

References: NEC 620.13; 620.14 and Table 620.14; 430.22(A)/(E) and Table 430.22(E); Table 310.16; Chapter 9 Table 8; and 250.122. Related circuit checks use 620.22, 620.23, 620.24, 620.51, 620.61 and 620.62, with terminal limits under 110.14(C). Section numbers and table text were checked against the NFPA 70 2008 edition text (sections 620.13, 620.14, 620.61, 620.62, Table 430.22(E), Chapter 9 Table 8) on 2026-11-14. Check the edition your jurisdiction adopted. We did not review the 2023 NEC text directly.

Use NFPA 70 edition information and free access to consult the applicable text. Wire Gauge Calculator calculated the tables on 2026-11-14: multiply nameplate current by the listed percentage or demand factor, then select the smallest listed 75 °C copper ampacity meeting the unrounded result. Displayed demand is rounded to one decimal place. All examples are hypothetical.

Not covered: escalator/moving-walk specifics, local amendments or manufacturer requirements. Confirm those separately, along with the engineer of record / AHJ’s approach to 430.24.

TOOLS

Calculate Your Wire Size

Use our professional calculators to determine the correct wire gauge, voltage drop, and ampacity for your electrical project.

Related Articles