Back to Tools
Pull Box Tool

Pull Box Size Calculator

// SIZE PULL BOXES FOR STRAIGHT PULLS, ANGLE PULLS, AND U PULLS WITH NEC 314.28 FORMULAS AND FIELD-READY REMINDERS //

Box Inputs

For angle pulls, U pulls, or splices, add the trade sizes of the other raceways on the same wall and row. Example: 2 in + 2 in = 4 in.

Minimum Dimension

Minimum Wall-to-Wall Distance
24 in
2023 NEC 314.28 controls bending space where raceways contain conductors 4 AWG or larger that are required to be insulated, or cables contain 4 AWG or larger conductors.
ScenarioStraight Pull
Formula8 × 3 = 24 in
Nearest Standard Box24 in

Straight pulls use 8 times the trade size of the largest raceway in the pulling direction.

Minimum code dimensions may pass inspection, but a larger box usually makes conductor pulling, training, and future maintenance easier.

NEC Rules

In the 2023 NEC, use 314.28(A)(1) when conductors pass straight through the enclosure without a change in direction. The minimum length in the pulling direction is 8 times the trade size of the largest raceway in that straight line.

Use 2023 NEC 314.28(A)(2) when conductors turn in the box or leave from the same wall. Measure from the raceway row to the opposite wall using 6 times the largest raceway in that row, then add the other raceway trade sizes on that same wall and row.

Straight pull: 8 x largest raceway trade size.
Angle pull: 6 x largest raceway + other raceways in the same row.
U pull: same base rule as angle pull, measured from the raceway row to the opposite wall.
If the enclosure also contains splices or taps, check free conductor length under NEC 300.14; NEC 314.16 box fill applies only to conductors 6 AWG and smaller.

Code References

Use this calculator to set a minimum enclosure dimension, then verify the actual box layout, conductor bending, and local amendments before installation.

NFPA 70 National Electrical Code

Formulas checked against the 2023 NEC (NFPA 70) sections 314.28(A)(1) and (A)(2) on 2026-11-08 (engine lib/pull-box-size.ts, revision 1751d7f). The tool returns straight-pull and row dimensions and the next listed size only; entry-to-exit spacing, box depth and 314.16 box fill are separate checks. Confirm the edition your jurisdiction has adopted. Outside the U.S., follow your local wiring rules and enclosure product standards instead.

Worked Examples

ScenarioInputsFormulaMinimum dimensionPractical takeaway
Straight pull3 in raceway8 x 324 in24 in is the code minimum in the pulling direction. The other dimensions are checked separately.
Angle pull3 in plus two 2 in raceways6 x 3 + 2 + 222 inThe two 2 in raceways add 4 in to the 6 x 3 base. Leaving them out undersizes the box.
U pull4 in plus one 3 in raceway6 x 4 + 327 in27 in is absent from this calculator’s size list. Its next listed dimension is 30 in.
Small-conductor splice box6 insulated 12 AWG conductors with spliceNot a 314.28 formulaUse NEC 314.16 volume rules314.16 volume applies here because the conductors are 6 AWG and smaller.

Field Tips

Start with the largest raceway because it usually controls the box size.
For angle and U pulls, sum the other raceways in the same row on that wall before ordering the enclosure.
Use the next larger standard box when conductors are stiff, large aluminum, or part of a difficult pull.
If the box contains splices or devices on conductors 6 AWG and smaller, do a separate NEC 314.16 volume check; for 4 AWG and larger, the 314.28 dimensions govern.
Check conduit fill, voltage drop, and conductor length before freezing the enclosure layout.

NEC vs IEC Notes

Projects outside the U.S. follow their national wiring rules, which may not use the NEC 314.28 wall-to-wall formulas at all. This calculator does not check any non-NEC standard; ask the authority having jurisdiction which rules and edition apply.

For mixed-specification projects, use this calculator as a planning check only. Confirm local raceway, enclosure, and conductor-bending requirements before fabrication or installation.

Pull Box FAQ

What is the NEC rule for a straight pull box?

2023 NEC 314.28(A)(1) requires the dimension in the pulling direction to be at least 8 times the trade size of the largest raceway. A 3 in raceway needs 24 in.

How do I size an angle pull or U pull box?

Use 2023 NEC 314.28(A)(2): start with 6 times the largest raceway on that wall and add the trade sizes of the other raceways in the same row. A 3 in raceway plus two 2 in raceways needs 22 in.

Does NEC 314.28 replace box fill calculations?

They cover different boxes. NEC 314.16 box-fill volume applies to conductors 6 AWG and smaller; NEC 314.28 sizes boxes with 4 AWG and larger conductors. If the box contains splices or taps, also check free conductor length under NEC 300.14.

Can conduit fill pass while pull box sizing fails?

Yes. A raceway can meet Chapter 9 fill rules and still need a larger pull box because large conductors need more room to bend and train safely.

When should I choose a box larger than the minimum?

Choose a larger box when the run includes 4 in or larger raceways, parallel sets, stiff aluminum conductors, or future service access needs. The code value is a minimum, so the next standard size up gives more working room.

Use this result with the conduit fill, box fill, voltage drop, and wire sizing tools before you finalize an enclosure for feeders, service conductors, or long raceway pulls.