Back to Tools
Professional Tool

Cable Size Calculator

// CALCULATE OPTIMAL CABLE SIZE BASED ON LOAD REQUIREMENTS //

INPUT_PARAMETERS
RECOMMENDED_CABLE_SIZE
Recommended Wire Size
8 AWG
copper
For Ampacity
10 AWG
40A rated
For Voltage Drop
8 AWG
3% VD
With 8 AWG copper
Ampacity (75°C)
40 A
Voltage Drop
1.91%
VD in Volts
4.58 V
Voltage at Load
235.4 V
StatusMEETS REQUIREMENTS
NEC_VOLTAGE_DROP_RECOMMENDATIONS

The National Electrical Code provides recommendations for maximum voltage drop to ensure efficient operation of electrical equipment. While these are recommendations (not requirements), they represent best practices for electrical installations.

3%

Branch Circuits

From panel to individual loads (outlets, lights, equipment)

2%

Feeders

From service entrance to subpanels

5%

Total Combined

Maximum from source to farthest outlet

UNDERSTANDING_CABLE_SIZING

What is Electrical Cable Sizing?

Cable sizing is the process of selecting the appropriate conductor size for an electrical circuit based on multiple factors including current capacity (ampacity), voltage drop limitations, and installation conditions. Proper cable sizing ensures safety, efficiency, and compliance with the National Electrical Code (NEC).

The Two Critical Sizing Criteria

1. Ampacity (Current Capacity)

The wire must be able to carry the required current without overheating. NEC Table 310.16 provides ampacity values based on conductor size, material, and insulation temperature rating.

2. Voltage Drop

The wire must be large enough to limit voltage drop to acceptable levels. Excessive voltage drop causes equipment malfunction, reduced efficiency, and can damage sensitive electronics.

Important: You must satisfy BOTH criteria. The final wire size is always the larger of the two requirements. A wire that has adequate ampacity but excessive voltage drop is undersized, and vice versa.

Voltage Drop Calculation

Single-Phase Voltage Drop Formula

VD = (2 × I × R × L) / 1000

Three-Phase Voltage Drop Formula

VD = (√3 × I × R × L) / 1000

VariableDescriptionUnit
VDVoltage dropVolts
ILoad currentAmperes
RWire resistanceOhms per 1000 feet
LOne-way cable lengthFeet
WIRE_SIZE_QUICK_REFERENCE

Ampacity and Resistance Reference (75°C Insulation)

This table shows ampacity values from NEC Table 310.16 and resistance values at 75°C for common wire sizes. Use this as a reference for quick cable sizing decisions.

AWG/kcmilCopper AmpsCopper Ω/1000ftAluminum AmpsAluminum Ω/1000ft
14153.070--
12201.930153.180
10301.210252.000
8400.764351.260
6550.491450.808
4700.308550.508
3850.245650.403
2950.194750.319
11100.154850.253
1/01250.1221000.201
2/01450.0971150.159
3/01650.0771300.126
4/01950.0611500.100

Values based on NEC Table 310.16 for 75°C rated insulation (THWN, XHHW). Derate for higher ambient temperatures or bundled conductors.

CABLE_SIZING_EXAMPLES

Real-World Cable Sizing Examples

Example 1: Residential Subpanel Feeder

Scenario: 100A subpanel feeder, 150 feet from main panel, 240V single-phase, copper wire, 3% maximum voltage drop.

Ampacity Requirement

1 AWG (110A)

VD with 1 AWG

3.85%

VD Requirement

1/0 AWG (2.29%)

Final Selection

1/0 AWG

Result: Although 1 AWG meets ampacity, it fails voltage drop. Use 1/0 AWG copper for both requirements.

Example 2: Commercial HVAC Unit

Scenario: 45A HVAC unit, 200 feet from panel, 208V three-phase, aluminum wire, 3% maximum voltage drop.

Ampacity Requirement

6 AWG (45A min)

VD with 6 AWG

5.42%

VD Requirement

2 AWG (2.31%)

Final Selection

2 AWG Aluminum

Result: Voltage drop is the limiting factor. 2 AWG aluminum provides 75A ampacity with acceptable voltage drop.

Example 3: Industrial Motor Circuit

Scenario: 60A motor, 50 feet from MCC, 480V three-phase, copper wire, 3% maximum voltage drop.

Ampacity Requirement

4 AWG (70A)

VD with 4 AWG

0.33%

VD Requirement

Any (all pass)

Final Selection

4 AWG Copper

Result: Short distance and high voltage make ampacity the only limiting factor. 4 AWG copper is adequate.

FACTORS_AFFECTING_CABLE_SIZE

Key Factors in Cable Sizing Decisions

Distance

Longer distances increase voltage drop proportionally. For every doubling of distance, voltage drop doubles. Long runs often require wire much larger than ampacity alone would suggest.

Voltage Level

Higher voltages allow longer distances with the same wire size. A 480V circuit can run 4× farther than 120V with the same percentage voltage drop, which is why industrial facilities use higher voltages.

Conductor Material

Aluminum has ~61% the conductivity of copper. For equivalent ampacity, aluminum must be 2 sizes larger (e.g., 2 AWG aluminum ≈ 4 AWG copper). However, aluminum is lighter and less expensive.

Ambient Temperature

Higher ambient temperatures reduce ampacity. In hot locations (attics, rooftops, hot climates), apply derating factors from NEC Table 310.15(B)(1). At 40°C ambient, 75°C wire is derated to 88%.

Conductor Bundling

When multiple current-carrying conductors share a raceway, ampacity must be derated per NEC Table 310.15(C)(1). 4-6 conductors = 80%, 7-9 = 70%, 10-20 = 50% of listed ampacity.

COMMON_MISTAKES

Common Cable Sizing Mistakes

1

Sizing for Ampacity Only

Many people select wire based solely on ampacity from NEC tables, ignoring voltage drop. For runs over 50-100 feet, voltage drop often requires larger wire than ampacity alone.

2

Using Wrong Distance

Distance should be measured as the actual cable run, not straight-line distance. Remember to account for vertical runs, routing around obstacles, and extra length for terminations.

3

Forgetting Derating Factors

Ampacity must be derated for high ambient temperatures and conductor bundling. A wire rated for 30A in ideal conditions may only carry 21A in a hot attic with multiple circuits.

4

Mismatching Copper/Aluminum

When switching between copper and aluminum, don't use the same size. Aluminum requires larger conductors and special terminations rated AL/CU or CO/ALR.

5

Using Nameplate Current Only

For motors, use NEC Table 430.248 (FLA values), not nameplate current. Also apply the 125% multiplier for continuous loads when sizing overcurrent protection.

Related Tools