CommercialDecember 13, 202415 min read

3-Phase Wire Sizing Guide

Complete guide to three-phase wire sizing for commercial and industrial applications. Covers delta and wye configurations, voltage relationships, power calculations, and proper conductor sizing.

Introduction to 3-Phase Power

Three-phase power is the backbone of commercial and industrial electrical systems worldwide. Unlike single-phase power found in most homes, three-phase systems deliver power through three conductors carrying alternating current 120 degrees out of phase with each other. This configuration provides significant advantages including more efficient power transmission, smoother motor operation, and higher power density.

Understanding three-phase wire sizing is essential for engineers, electricians, and facility managers working with commercial buildings, manufacturing plants, data centers, and any installation requiring significant power. This guide covers the fundamentals of 3-phase systems and provides practical guidance for proper conductor sizing.

3-Phase Power Fundamentals

Voltage Relationships

In three-phase systems, two voltage values are commonly referenced: line-to-line (phase-to-phase) voltage and line-to-neutral (phase-to-neutral) voltage. The relationship between them involves the square root of 3:

V(line-to-line) = V(line-to-neutral) × √3

√3 ≈ 1.732. Example: 480V L-L system has 277V L-N voltage.

Common 3-Phase Voltages

System TypeLine-to-LineLine-to-NeutralTypical Use
208Y/120V208V120VSmall commercial, multi-family
480Y/277V480V277VCommercial, industrial
240V Delta240VN/A (or 120V high-leg)Older commercial
600Y/347V600V347VCanadian industrial

Delta vs Wye Configurations

Wye (Star) Configuration

In a wye configuration, one end of each phase winding is connected to a common neutral point. This provides access to two voltage levels and is the most common configuration for building power distribution.

  • Four-wire system: Three phase conductors plus neutral
  • Two voltage levels: Line-to-line and line-to-neutral
  • Neutral carries unbalanced current: Size neutral for maximum unbalanced load
  • Common example: 480Y/277V - 480V for motors, 277V for lighting

Delta Configuration

In a delta configuration, phase windings are connected end-to-end forming a triangle. This creates a three-wire system with only one voltage level available between phases.

  • Three-wire system: No inherent neutral point
  • Single voltage level: Line-to-line only
  • High-leg delta: Can create 120V with center-tapped transformer
  • Common use: Motor loads, older installations

High-Leg Delta Caution

In high-leg (wild-leg) delta systems, one phase is 208V to ground instead of 120V. This phase must be identified (typically with orange marking) and cannot be used for 120V loads. Always verify voltage before connecting loads.

3-Phase Power Calculations

Power Formulas

P = √3 × V(L-L) × I × PF

Three-phase power in watts. V(L-L) = line-to-line voltage, I = line current, PF = power factor

I = P / (√3 × V × PF)

Calculate line current from power. Essential for wire sizing.

Apparent Power (kVA)

S = √3 × V(L-L) × I / 1000

Apparent power in kVA. Used for transformer and conductor sizing.

Wire Sizing for 3-Phase Circuits

Step-by-Step Sizing Process

  • Step 1: Calculate the full load current using the power formula
  • Step 2: Apply NEC continuous load factor (×1.25) if applicable
  • Step 3: Select wire based on ampacity from NEC Table 310.16
  • Step 4: Calculate voltage drop and upsize if necessary
  • Step 5: Apply derating factors for temperature and conduit fill

3-Phase Voltage Drop

VD = (√3 × K × I × D) / CM

Where K = 12.9 (copper) or 21.2 (aluminum), I = amps, D = one-way distance (ft), CM = circular mils

3-Phase Wire Size Reference

The following table shows recommended copper wire sizes for 3-phase 480V circuits at various distances (based on 3% voltage drop):

Load (Amps)50 ft100 ft200 ft300 ft
20A12 AWG12 AWG10 AWG8 AWG
50A6 AWG6 AWG4 AWG2 AWG
100A3 AWG1 AWG2/0 AWG3/0 AWG
200A3/0 AWG250 kcmil350 kcmil500 kcmil
400A500 kcmil2×3/0 AWG2×300 kcmil2×400 kcmil

Neutral Conductor Sizing

In 4-wire wye systems, the neutral conductor carries the unbalanced current between phases. For linear loads, if phases are perfectly balanced, neutral current is zero. However, practical installations are rarely perfectly balanced.

Linear Loads

For traditional linear loads (lighting, heating, motors), the neutral can often be sized smaller than the phase conductors per NEC 220.61:

  • First 200A of neutral load: 100%
  • Remainder over 200A: 70%
  • Minimum size: Per NEC 250.24(C) for service

Non-Linear Loads (Harmonics)

Harmonic Current Warning

Non-linear loads (computers, VFDs, LED drivers, electronic ballasts) generate triplen harmonics (3rd, 9th, 15th, etc.) that add in the neutral conductor. For buildings with significant electronic loads, the neutral may need to be sized at 200% of phase conductors to handle harmonic currents.

Equipment Grounding Conductor

The equipment grounding conductor (EGC) is sized based on the overcurrent protection device per NEC Table 250.122:

Overcurrent Device (Amps)Copper EGCAluminum EGC
60A10 AWG8 AWG
100A8 AWG6 AWG
200A6 AWG4 AWG
400A3 AWG1 AWG
600A1 AWG2/0 AWG

Motor Circuit Considerations

Three-phase motors require special consideration for wire sizing due to starting currents and continuous operation:

  • Full Load Current: Use NEC Table 430.250, not nameplate
  • Branch Circuit Size: 125% of motor FLA minimum
  • Overload Protection: Typically 115-125% of nameplate FLA
  • Short Circuit Protection: Size per NEC Table 430.52

Practical Example

Problem: Size conductors for a 75 kVA, 480V 3-phase load, 200 feet from the panelboard, with a power factor of 0.85.

  • Calculate current: I = 75,000 / (√3 × 480) = 90.2A
  • Continuous load: 90.2A × 1.25 = 112.8A
  • Minimum for ampacity: 1 AWG copper (130A at 75°C)
  • Check voltage drop at 1 AWG: Approximately 3.5% - marginal
  • Upsize to 1/0 AWG: Approximately 2.8% - acceptable
  • Final selection: 1/0 AWG copper, 125A breaker

Conclusion

Three-phase wire sizing requires understanding of power relationships, voltage configurations, and the special requirements of commercial and industrial loads. By following NEC requirements for ampacity and considering voltage drop for longer runs, you can design safe and efficient three-phase power distribution systems.

Use our Voltage Drop Calculator to verify your designs, and always consult with a licensed professional engineer for complex industrial installations.

TOOLS

Calculate Your Wire Size

Use our professional calculators to determine the correct wire gauge, voltage drop, and ampacity for your electrical project.

Related Articles