3 Phase Wire Size Calculator

// SIZE THREE PHASE CONDUCTORS FROM LOAD, VOLTAGE, RUN LENGTH, MATERIAL, CONTINUOUS-DUTY LOAD, AND VOLTAGE-DROP TARGET //

THREE_PHASE_INPUTS
RECOMMENDED_CONDUCTOR

Load Current

80.0 A

Design Amps

100.0 A

Meets ampacity and voltage drop

3 AWG

100 A ampacity, 5.1 V drop, 1.06% voltage drop.

Ampacity-only minimum

3 AWG

Voltage drop may require upsizing beyond this minimum on long three phase runs.

CALCULATION_NOTES

Three phase current uses I = kW x 1000 / (sqrt(3) x V x PF x efficiency), or I = kVA x 1000 / (sqrt(3) x V). Voltage drop uses the one-way circuit length and conductor resistance.

Ampacity values are planning references based on common 75C copper and aluminum conductor columns. Final installations still need terminal temperature, insulation type, ambient correction, conductor bundling, equipment instructions, overcurrent protection, and local code review.

CANDIDATE_SIZES
ConductorAmpacityVoltage DropStatus
14 AWG20 A13.29%Check
12 AWG25 A8.36%Check
10 AWG35 A5.24%Check
8 AWG50 A3.31%Check
6 AWG65 A2.13%Check
4 AWG85 A1.33%Check
3 AWG100 A1.06%Pass
2 AWG115 A0.84%Pass