Volver a herramientas
Planeación de subpanel

Guía de dimensionamiento de subpanel para garaje separado

// PLANEA UN ALIMENTADOR DE GARAJE DE 30 A A 100 A CON AMPACIDAD, CAÍDA DE VOLTAJE, LLENADO DE CONDUIT, TIERRA FÍSICA, NEUTRO AISLADO Y EJEMPLOS DE CARGA ANTES DE ABRIR ZANJA O MONTAR EL PANEL. //

GARAGE_FEEDER_PLAN

Un alimentador para garaje separado combina cargas residenciales, canalización exterior, unión del subpanel, caída de voltaje en tramos largos y futuras cargas de taller. Empieza con cargas reales y revisa por separado alimentador, tierra física, conduit y electrodos.

Detached building

NEC 225 covers outside feeders and branch circuits to a separate structure, while NEC 250.32 decides grounding and bonding at the garage

4-wire feeder

Modern detached-garage subpanels normally need two hots, an insulated neutral when used, and an equipment grounding conductor with neutral isolated

Voltage drop

A 60 A 120/240 V feeder at 150 ft may pass ampacity with 6 AWG copper but often needs 4 AWG copper or 2 AWG aluminum for about 3% drop

QUICK_ANSWER

Resumen

  • Choose feeder ampacity from calculated garage loads, not from panel size alone
  • Use a 4-wire feeder and isolate neutral from ground in the detached subpanel
  • Check voltage drop early because 100-200 ft garage runs often drive conductor upsizing
  • Run conduit-fill and pull checks before buying UF cable, THWN-2 conductors, or PVC
  • Confirm grounding electrodes and disconnect rules with the local AHJ before trenching
ENTITY_DEFINITIONS

Definiciones clave

Detached-garage subpanel

A detached-garage subpanel is a panelboard in a separate building supplied by a feeder from the main service

Feeder

A feeder is a conductor set that carries power from service equipment or another panel to downstream branch-circuit overcurrent devices

Grounding electrode system

A grounding electrode system is the rod, concrete-encased electrode, metal water pipe, or other electrode connection required to bond the separate structure to earth

SIZING_WORKFLOW

Flujo de dimensionamiento

Step 1 - load list

Add lighting, receptacles, compressor, mini-split, door opener, freezer, welder, EVSE, and spare circuits. A 5 hp compressor or 40 A welder changes the feeder more than ordinary lights

Step 2 - feeder ampacity

Pick 30 A, 60 A, 90 A, or 100 A from calculated load and diversity. Use NEC Table 310.16 with the correct copper or aluminum column and terminal temperature

Step 3 - voltage drop

Enter one-way distance in the voltage-drop calculator. For a 60 A feeder at 150 ft, compare 6 AWG copper, 4 AWG copper, and 2 AWG aluminum before deciding

Step 4 - grounding and bonding

Under NEC 250.32, keep neutral and grounding bars separate in the garage panel and size the equipment grounding conductor from NEC 250.122

Step 5 - raceway and trench

Check Chapter 9 conduit fill, burial depth, wet-location conductor markings such as THWN-2, expansion fittings, and local inspection requirements before excavation

WORKED_EXAMPLES

Ejemplos prácticos

60 A hobby shop at 120 ft

Loads include 12 A lighting and receptacles, 18 A compressor, and a 24 A dust collector on a 120/240 V feeder

Ampacity can start around 6 AWG copper THWN-2 at 75C terminals, but voltage drop may justify 4 AWG copper for motor starting margin

100 A workshop at 180 ft

Loads include a 48 A EV charger, 30 A welder receptacle, 16 A mini-split, and general outlets with load diversity documented

Ampacity may point to 3 AWG copper or 1 AWG aluminum at 75C, while voltage drop often pushes the practical choice larger

30 A storage garage at 80 ft

Loads include LED lighting, receptacles, door opener, and a small freezer with no welder or EVSE

10 AWG copper may satisfy ampacity, but use the calculator to see whether 8 AWG copper better protects 120 V freezer starting voltage

GARAGE_FEEDER_COMPARISON

Comparación de alimentadores

Plan de garajeBreaker típicoRevisión inicial del conductorRiesgo de caída de voltajeNota de planeación
Storage only30 A 120/240 V10 AWG Cu or 8 AWG Al checkMedium after 100 ftGood for lights, outlets, opener, freezer
Hobby shop60 A 120/240 V6 AWG Cu or 4 AWG Al checkHigh after 120 ftCommon point where voltage drop drives upsizing
Heavy workshop100 A 120/240 V3 AWG Cu or 1 AWG Al checkHigh after 150 ftCheck terminals, conduit fill, and future EVSE
Single welder circuit50 A branch or feeder allowance6 AWG Cu branch checkMedium after 75 ftWelder duty cycle may affect sizing under NEC 630
IEC outbuilding32-63 A distribution circuit6-16 mm2 check by methodProject specificUse IEC 60364 installation method, grouping, and Clause 525 voltage drop
CODE_REFERENCES

Referencias de código

Usa estos enlaces y artículos como puntos de revisión, no como sustituto del permiso. Las reglas locales pueden cambiar detalles de zanja, desconexión y puesta a tierra.

NEC 225

Outside feeders and branch circuits to a separate building, including disconnect and supply rules for detached structures

NEC 250.32 and 250.122

Grounding electrodes, bonding, neutral isolation, and equipment grounding conductor sizing for feeders to separate buildings

NEC 310 and Chapter 9

Ampacity tables, adjustment factors, terminal temperature limits, and raceway fill checks for THWN-2 or cable assemblies

IEC 60364-5-52

IEC projects check current-carrying capacity, installation method, grouping, ambient temperature, and voltage drop under Clause 525

FIELD_CHECKLIST

Lista en campo

  • Document one-way feeder distance and voltage at the source
  • List every 120 V and 240 V load before choosing panel amp rating
  • Verify four conductors when a neutral is required and keep neutral isolated in the garage panel
  • Size the equipment grounding conductor separately from the neutral
  • Check conduit fill, pull length, sweeps, expansion fittings, and wet-location conductor marking
  • Confirm permits, burial depth, GFCI rules, and local amendments with the AHJ
FAQ

FAQ de alimentador para garaje separado

Can I install a 100 A panel if my load is only 45 A?

Often yes, but the feeder breaker and conductor ampacity still govern usable load. A larger panel gives spaces, not extra amps without a matching feeder

Does a detached garage need ground rods?

Under NEC 250.32, a detached building supplied by feeders or branch circuits typically needs a grounding electrode system such as rods, plus an equipment grounding conductor back to the source

Can I bond neutral and ground in the garage subpanel?

For modern 4-wire feeders, no. Keep neutral isolated and bond the equipment grounding conductor and grounding electrode conductor to the panel enclosure

What wire size is common for a 60 A garage subpanel?

6 AWG copper is a common ampacity starting point at suitable terminals, but a 120-150 ft run may need 4 AWG copper or larger to meet a 3% voltage-drop target

Should DIYers use this guide for final installation?

DIYers can use the numbers to plan questions and material estimates, but detached-building feeders involve permits, trenching, grounding, and inspection, so final work should follow the AHJ and a licensed electrician where required

NEXT_STEPS

Calcula antes de abrir zanja

Compara tamaño de alimentador, caída de voltaje, llenado de conduit y ampacidad antes de comprar conductores o cortar conduit.