// SCREEN TRANSFORMER PRIMARY AND SECONDARY CONDUCTOR SIZE FROM KVA, VOLTAGE, RUN LENGTH, AND TERMINAL BASIS BEFORE FINAL CODE REVIEW //

TRANSFORMER_INPUTS

Enter transformer nameplate size in kVA for a first-pass conductor screen.

Distance in feet from the source equipment to the transformer primary terminals.

Distance in feet from the transformer secondary to the downstream equipment.

Drop Target
3%
Recommendations must clear both ampacity and this drop limit.
TRANSFORMER_RESULT
Recommended Primary
4 AWG

21.1 mm² | 85.0 A

Recommended Secondary
2/0 AWG

67.4 mm² | 175 A

Primary Current
54.1 A
Required ampacity: 67.7 A
Secondary Current
125 A
Required ampacity: 156 A
Voltage Ratio
2.31:1
Primary Est. Drop
0.36%
1.73 V
Secondary Est. Drop
0.91%
1.88 V
Planning Note

This tool screens conductor size only. Final transformer work still needs separate review of overcurrent protection, secondary protection method, taps, grounding, terminals, and local amendments.

PRIMARY_CANDIDATES
Line Voltage
480 V
Run Length
60 ft
Design Basis
125%
SizeAmpacityEst. DropStatus
14 AWG
2.1 mm²
20.0 A3.60%Upsize
12 AWG
3.3 mm²
25.0 A2.26%Upsize
10 AWG
5.3 mm²
35.0 A1.42%Upsize
8 AWG
8.4 mm²
50.0 A0.90%Upsize
6 AWG
13.3 mm²
65.0 A0.58%Upsize
4 AWG
21.1 mm²
85.0 A0.36%Pass
SECONDARY_CANDIDATES
Line Voltage
208 V
Run Length
90 ft
Material
Copper
SizeAmpacityEst. DropStatus
14 AWG
2.1 mm²
20.0 A28.74%Upsize
12 AWG
3.3 mm²
25.0 A18.07%Upsize
10 AWG
5.3 mm²
35.0 A11.33%Upsize
8 AWG
8.4 mm²
50.0 A7.15%Upsize
6 AWG
13.3 mm²
65.0 A4.60%Upsize
4 AWG
21.1 mm²
85.0 A2.88%Upsize
FIELD_NOTES

Primary and secondary conductor rules can change with the transformer overcurrent protection arrangement. Use this page as a planning screen, not a final code answer.

The lower-voltage side usually carries much more current, so secondary conductors often need more upsizing than the primary.

Voltage drop shown here is only for the selected primary or secondary run. Review the full feeder or branch-circuit path before release.

WATCH_ITEMS

Transformer secondary tap rules and protection location are not modeled here.

Neutral, grounding electrode, and equipment grounding conductor sizing require separate checks.

Large dry-type transformers can also need ventilation, lug, and enclosure coordination beyond conductor ampacity.