// SIZE THREE PHASE CONDUCTORS FROM LOAD, VOLTAGE, RUN LENGTH, MATERIAL, CONTINUOUS-DUTY LOAD, AND VOLTAGE-DROP TARGET //

THREE_PHASE_INPUTS
RECOMMENDED_CONDUCTOR

Load Current

80.0 A

Design Amps

100.0 A

Meets ampacity and voltage drop

3 AWG

100 A ampacity, 5.1 V drop, 1.06% voltage drop.

Ampacity-only minimum

3 AWG

Voltage drop may require upsizing beyond this minimum on long three phase runs.

CALCULATION_NOTES

Three phase current uses I = kW x 1000 / (sqrt(3) x V x PF x efficiency), or I = kVA x 1000 / (sqrt(3) x V). Set efficiency to 1 for electrical input kW. Do not size motor circuits from kW: use the NEC Table 430.250 full-load current in the Motor Wire Size Calculator. Voltage drop uses the one-way circuit length and stranded conductor resistance (NEC Chapter 9 Table 8).

Ampacity values are planning references based on common 75C copper and aluminum conductor columns, with the NEC 240.4(D) limits for 14, 12 and 10 AWG applied. Final installations still need terminal temperature, insulation type, ambient correction, conductor bundling, equipment instructions, overcurrent protection, and local code review.

CANDIDATE_SIZES
ConductorAmpacityVoltage DropStatus
4 AWG85 A1.33%Check
3 AWG100 A1.06%Pass
2 AWG115 A0.84%Pass
1 AWG130 A0.67%Pass
1/0 AWG150 A0.53%Pass
2/0 AWG175 A0.42%Pass
3/0 AWG200 A0.33%Pass
4/0 AWG230 A0.26%Pass