Back to Tools
Generator Tool

Generator Wire Size Calculator

// SCREEN FEEDER CONDUCTOR SIZE FOR GENERATOR INLETS, TRANSFER SWITCHES, AND STANDBY DISTRIBUTION RUNS FROM KW, VOLTAGE, DISTANCE, AND DROP TARGET //

GENERATOR_INPUTS

Enter generator nameplate real-power output in kilowatts for a first-pass conductor screen.

Pick the actual generator output or feeder voltage so current and drop are checked on the right basis.

Use 1.00 for resistive or nameplate kW planning, or enter a lower PF when generator loading is motor-heavy.

Enter one-way conductor length in feet between the generator source and the connected equipment.

Enable this when you want a 125% planning screen for sustained generator loading instead of a straight nameplate check.

GENERATOR_RESULT
Calculated Current
50.0 A

12 kW at 240 V, single-phase, PF 1.00

Required Ampacity
50.0 A

100% design screen shown for intermittent or nameplate-based planning.

Recommended Conductor
8 AWG

8.4 mm² equivalent, 50.0 A ampacity screen, 5.73 V estimated drop (2.39%).

Drop Target
3%
Wiring Use
Inlet / transfer / feeder
Ampacity Basis
75C terminals
CONDUCTOR_OPTIONS

Each row checks the selected conductor material and terminal rating against both required ampacity and estimated voltage drop for the entered run length.

SizeAmpacityResistanceVoltage DropStatus
14 AWG
2.1 mm²
20.0 A3.0700 ohm/kft23.0 V / 9.59%Upsize
12 AWG
3.3 mm²
25.0 A1.9300 ohm/kft14.5 V / 6.03%Upsize
10 AWG
5.3 mm²
35.0 A1.2100 ohm/kft9.07 V / 3.78%Upsize
8 AWG
8.4 mm²
50.0 A0.7640 ohm/kft5.73 V / 2.39%Pass
6 AWG
13.3 mm²
65.0 A0.4910 ohm/kft3.68 V / 1.53%Pass
4 AWG
21.1 mm²
85.0 A0.3080 ohm/kft2.31 V / 0.96%Pass
3 AWG
26.7 mm²
100 A0.2450 ohm/kft1.84 V / 0.77%Pass
2 AWG
33.6 mm²
115 A0.1940 ohm/kft1.46 V / 0.61%Pass
1 AWG
42.4 mm²
130 A0.1540 ohm/kft1.16 V / 0.48%Pass
1/0 AWG
53.5 mm²
150 A0.1220 ohm/kft0.91 V / 0.38%Pass
2/0 AWG
67.4 mm²
175 A0.0967 ohm/kft0.73 V / 0.30%Pass
3/0 AWG
85.0 mm²
200 A0.0766 ohm/kft0.57 V / 0.24%Pass
4/0 AWG
107.2 mm²
230 A0.0608 ohm/kft0.46 V / 0.19%Pass
250 kcmil
126.7 mm²
255 A0.0515 ohm/kft0.39 V / 0.16%Pass
300 kcmil
152.0 mm²
285 A0.0429 ohm/kft0.32 V / 0.13%Pass
350 kcmil
177.3 mm²
310 A0.0367 ohm/kft0.28 V / 0.11%Pass
400 kcmil
202.7 mm²
335 A0.0321 ohm/kft0.24 V / 0.10%Pass
500 kcmil
253.3 mm²
380 A0.0258 ohm/kft0.19 V / 0.08%Pass
FIELD_NOTES

Use this calculator for fixed wiring between a generator, inlet, transfer switch, disconnect, or downstream distribution equipment. If you are sizing a portable cord set instead, use the extension cord tool and verify the cord listing.

  • Generator feeder conductors still need final review for overcurrent protection, transfer equipment listings, and any neutral or grounding rules that apply to the installation.
  • Voltage-drop limits here are planning targets, not direct NEC mandates. Sensitive equipment and motor starting often justify a tighter drop limit.
  • This tool is for fixed wiring between a generator and downstream equipment, not for flexible portable cord sets or temporary wiring approvals.
WORKED_EXAMPLES

7.5 kW portable generator to 30A inlet

At 240 V single-phase and 60 ft one way, the calculated current is about 31.3 A. 10 AWG copper has enough ampacity but usually pushes above a tight 2% drop limit, so 8 AWG becomes the cleaner fixed-wiring choice.

20 kW standby generator to transfer switch

A 20 kW, 120/240 V single-phase unit delivers about 83.3 A at PF 1.00. With a 100 ft run and 3% target, 3 AWG copper can be a practical planning result before final OCPD, neutral sizing, and grounding checks.

60 kW three-phase generator feeder

On 480 V three-phase at PF 0.9, load current is roughly 80 A. Voltage drop is modest at this voltage, so the selection is often driven by ampacity, terminals, and installation conditions rather than distance alone.