Back to Tools
Material Calculator

Wire Weight Calculator

// CALCULATE WIRE WEIGHT FOR COPPER AND ALUMINUM CONDUCTORS //

INPUT PARAMETERS
WEIGHT CALCULATION
Total Weight
1.98
lbs
Total Weight
0.90
kg
Weight per 1000ft
19.8 lbs
Wire Diameter
2.05 mm
0.0808"
Wire Specifications - 12 AWG Copper
Diameter
2.05 mm
Cross-Section
3.31 mm²
Density
8.96 g/cm³
Material Comparison
Aluminum is 70% lighter than copper
Weight savings: 1.38 lbs for this run
COPPER VS ALUMINUM COMPARISON

Understanding the weight differences between copper and aluminum conductors is crucial for installation planning, structural calculations, and cost estimation. This comparison shows the actual weight impact for your specific wire run.

PropertyCopperAluminumDifference
Weight (lbs/1000ft)19.86.070% lighter
Your run (100 ft × 1)1.98 lbs0.60 lbs1.38 lbs saved
WHY CALCULATE WIRE WEIGHT

Why Wire Weight Calculations Matter

Accurate wire weight calculations are essential for multiple aspects of electrical installation planning and project management. Whether you're planning a residential renovation or a large-scale commercial project, understanding wire weight impacts safety, costs, and installation logistics.

Structural Support Design

Cable trays, supports, and hangers must be sized to safely carry the weight of all installed conductors. Underestimating wire weight can lead to structural failures.

Cable Pulling Calculations

Wire weight directly affects pulling tension in conduit runs. Excessive tension can damage insulation and conductors, especially in long or complex runs.

Shipping & Logistics

Freight costs are often calculated by weight. Large wire orders can weigh thousands of pounds, significantly impacting project budgets and delivery requirements.

Material Handling

Planning for appropriate lifting equipment, spool stands, and crew size requires accurate weight estimates to ensure safe material handling on site.

How Wire Weight is Calculated

Wire Weight Formula

Total Weight = (Weight per 1000ft ÷ 1000) × Length × Conductor Count

Wire weight is determined by the conductor material density, cross-sectional area, and length. Copper has a density of 8.96 g/cm³ while aluminum is only 2.70 g/cm³, making aluminum approximately 70% lighter than copper for the same conductor dimensions.

FactorDescriptionImpact on Weight
Wire GaugeAWG size determines conductor cross-sectional areaLower AWG = larger diameter = heavier
MaterialCopper or aluminum conductorCopper is 3.3× denser than aluminum
LengthTotal conductor length in feet or metersLinear relationship - double length = double weight
InsulationType and thickness of insulation jacketAdds 5-15% to bare conductor weight
WIRE WEIGHT REFERENCE TABLE

Complete Wire Weight Reference (Bare Conductor)

This table shows the weight per 1000 feet for bare copper and aluminum conductors. Add approximately 5-15% for insulated wire weight depending on insulation type and thickness.

AWGDiameter (in)Diameter (mm)Area (mm²)Copper (lbs/1000ft)Aluminum (lbs/1000ft)
10.28937.3542.41253.376.9
20.25766.5433.62200.961.0
30.22945.8326.67159.348.4
40.20435.1921.15126.338.4
60.16204.1113.3079.524.1
80.12853.268.3750.015.2
100.10192.595.2631.49.6
120.08082.053.3119.86.0
140.06411.632.0812.43.8
1/00.32498.2553.49319.597.0
2/00.36489.2767.43402.8122.3
3/00.409610.4085.01507.9154.2
4/00.460011.68107.22640.5194.5

Note: Weights shown are for bare conductors. Insulated wire will weigh more due to the jacket material.

COPPER VS ALUMINUM ANALYSIS

Copper vs Aluminum: A Complete Comparison

The choice between copper and aluminum conductors involves tradeoffs between weight, conductivity, cost, and installation requirements. Understanding these differences helps you make the right choice for your project.

Copper Conductors

Density8.96 g/cm³
Conductivity100% IACS
Relative Weight3.3× heavier
Typical CostHigher $/lb

<strong>Best for:</strong> Small gauge wire (14-6 AWG), residential branch circuits, terminations at equipment rated for copper only

Aluminum Conductors

Density2.70 g/cm³
Conductivity61% IACS
Relative Weight70% lighter
Typical CostLower $/lb

<strong>Best for:</strong> Large feeder and service conductors (4/0 and larger), long runs, utility applications, cost-sensitive projects

When to Use Each Material

ApplicationRecommendedReasoning
Residential Branch CircuitsCopperSmaller sizes, easier terminations, code requirements
Service Entrance (200A+)AluminumCost savings, weight reduction for large conductors
Long Feeder RunsAluminumSignificant weight and cost savings over long distances
Industrial EquipmentCopperBetter conductivity, vibration resistance, terminal compatibility
Utility DistributionAluminumLighter weight for overhead lines, lower material costs
PRACTICAL APPLICATIONS

Real-World Wire Weight Applications

Example 1: Cable Tray Load Calculation

<strong>Scenario:</strong> A 100-foot cable tray run will carry 4 sets of 4/0 AWG aluminum feeders (3 conductors + ground per set = 16 conductors total).

Weight per 1000ft

194.5 lbs

Conductors

16

Run Length

100 ft

Total Weight

311.2 lbs

<strong>Result:</strong> Cable tray must be rated for at least 3.11 lbs/ft plus safety factor. A 6" wide ladder tray with 100 lb/ft rating is adequate with significant margin.

Example 2: Wire Order Shipping Estimate

<strong>Scenario:</strong> Ordering wire for a commercial building: 2000ft of 12 AWG copper (branch circuits) + 500ft of 4/0 copper (feeders).

12 AWG × 2000ft

39.5 lbs

4/0 AWG × 500ft

320.3 lbs

Total Wire

359.8 lbs

With Packaging

~400 lbs

<strong>Result:</strong> Order requires approximately 400 lbs shipping weight. Consider freight vs. parcel shipping options and delivery equipment needs.

Example 3: Conduit Pull Weight Factor

<strong>Scenario:</strong> Pulling 3 × 2/0 AWG copper THHN through 200ft of 2" EMT with two 90° bends.

Weight per 1000ft

402.8 lbs

3 Conductors × 200ft

241.7 lbs

Coefficient of Friction

0.35

Est. Pull Tension

~450 lbs

<strong>Result:</strong> Significant pulling tension required. Use proper lubricant and ensure pulling eye is rated for the load. Consider intermediate pull points for longer runs.

COMMON MISTAKES

Common Wire Weight Calculation Mistakes

1

Forgetting Insulation Weight

Bare conductor weights don't include insulation. For THHN/THWN, add approximately 5-10% to bare weight. For larger insulation types like XHHW or USE, add 10-15%.

2

Not Accounting for All Conductors

Remember to count ground wires and neutral conductors when calculating total weight. A 3-phase circuit typically has 4-5 conductors, not 3.

3

Comparing Different Materials at Same AWG

When comparing copper vs. aluminum, remember that aluminum requires a larger conductor size for equivalent ampacity. Compare 4/0 aluminum to 2/0 copper for 200A service, not the same AWG.

4

Ignoring Spool and Packaging Weight

Wooden reels can add 50-200+ lbs to large wire orders. Factor in packaging weight for shipping estimates and material handling equipment needs.

5

Not Adding Safety Factor for Supports

Cable tray and support sizing should include at least 1.5× safety factor above calculated weight, plus allowance for future additions and dynamic loading during installation.